Manufactured by:Chlorine Specialties, Inc. based inBurlingame, CALIFORNIA (USA)
This single pass across the channel diffuser shown is designed to be lowered into wall brackets. Operating evidence indicates that this type of diffuser should be limited to channels carrying less than 10 mgd or those wider than 5 ft. Beyond these limits there is a significant decrease in mixing efficiency. Therefore in these instances the diffuser should be supplemented by a mechanical mixer ...
Manufactured by:Chlorine Specialties, Inc. based inBurlingame, CALIFORNIA (USA)
This single pass across the channel diffuser shown in Fig. 5 is designed to be lowered into wall brackets. Operating evidence indi¬cates that this type of diffuser should be limited to channels carry¬ing less than 10 mgd or those wider than 5 ft. Beyond these limits there is a significant decrease in mixing efficiency. Therefore in these instances the diffuser should be supplemented by a ...
Manufactured by:Chlorine Specialties, Inc. based inBurlingame, CALIFORNIA (USA)
The C-266 diffuser (Fig. 3) discharges the chlorine solution across the diameter of the pipe. At this velocity the chlorine solution will easily traverse the diameter of a 36 in. pipe. This across the pipe jet action will insure a thorough mix of the chlorine solution at 10 pipe diameters downstream from the injection point. These diffusers are for pipes larger than 24 in. They are the new ...
Manufactured by:Chlorine Specialties, Inc. based inBurlingame, CALIFORNIA (USA)
This diffuser shown in Fig. 4 is lor pipes larger than 36 inches but can be used for smaller pipes. Similarly, the jet velocity of this diffuser will be 23-26 ft/sec but in this case the diffuser must be installed with the jets directed upstream counter to the pipeline flow. This arrangement insures a thorough mix ten pipe diameters downstream for the injection ...
Manufactured by:Chlorine Specialties, Inc. based inBurlingame, CALIFORNIA (USA)
This diffuser is for pipes up to and includ¬ing 24 inches in diameter (see Fig. 2). It is designed to inject the chlorine solution into the center of the pipe. This will result in a complete mix of process flow and chlorine solution 10 pipe diameters downstream from the diffuser provided the pipeline flow is sufficient to generate a Reynolds Number (NR) of 3000 or greater. These diffusers are ...